E5CK
5–5
Ă• In this mode, manual operation is possible, and the MANU" LED lights.
Ă• When this mode is selected, the manipulated variable that was active immediately
before the mode was switched to is output. To change the manipulated variable, use
the
or keys. If this mode is switched to during autoĆtuning, autoĆtuning is
canceled.
Ă• To select this mode when in the level 0 to 2 modes, press the
and keys simulĆ
taneously for 1 second minimum. To exit this mode, press the
and keys
simultaneously again for 1 second minimum. The mode changes to the level 0 mode.
Ă• Manual MV" is the only parameter available in this mode.
Manual MV
Ă• Sets the manipulated variable for manual operation. When you press the or
keys, the manipulated variable is changed.
Ă• The process value is displayed on the No.1 display and the manipulated variable is
displayed on the No.2 display.
Ă• The manual MV is held when the power is interrupted.
Control Method Setting Range
Unit Default
Standard -5.0 to 105.0 % 0.0
Heating and cooling -105.0 to 105.0 % 0.0
ĂRelated description
3.8 Adjusting Control Operation/Manual operation (page 3Ć22)
Manual Mode
Function
Setting
See