E5CK
5–21
Control period (heat)
Control period (cool)
Conditions of Use
Relay, SSR or voltage output must set as
the outputs, and the control must be set to
advanced PID control, standard control or
heating and cooling control.
Ă• Sets the pulse output period. Set the control period taking the control characteristics
and life expectancy of the controller into consideration.
Ă• In a standard control system, use the control period (heat)" parameter. The control
period (cool)" parameter cannot be used.
Ă• In a heating and cooling control system, the control period can be set independently
for heating and cooling. Use the control period (heat)" parameter to set the heating
side control period, and use the control period (cool)" parameter to set the cooling
side control period.
Parameter Setting Range
Unit Default
Control period (heat) 1 to 99 Second 20
Control period (cool) 1 to 99 Second 20
ĂRelated description
3.3 Setting Output Specifications (page 3Ć7)
ĂRelated parameters
Control output 1 assignment" Control output 2 assignment" (setup mode)
Level 1 Mode
Function
Setting
See