Terminal types
Manufac-
turer
Ferrule
model
*1
Applica-
ble wire
(mm
2
(A
WG))
Crimping tool
All terminals except
ground terminals
Phoenix
Contact
AI0,34-8
0.34 (#22) Phoenix Contact (Applicable wire size given
in parentheses)
CRIMPFOX 6 (0.25 to 6 mm
2
, AWG24 to
10)
AI0,5-8
0.5 (#20)
AI0,5-10
AI0,75-8 0.75 (#18)
AI0,75-10
AI1,0-8 1.0 (#18)
AI1,0-10
AI1,5-8 1.5 (#16)
AI1,5-10
Ground terminals AI2,5-10
2.0
*2
All terminals except
ground terminals
Weidmul-
ler
H0.14/12 0.14 (#26) Weidmuller (Applicable wire size given in
parentheses)
PZ6 Roto (0.14 to 6 mm
2
, AWG26 to 10)
H0.25/12
0.25 (#24)
H0.34/12 0.34 (#22)
H0.5/14 0.5 (#20)
H0.5/16
H0.75/14 0.75 (#18)
H0.75/16
H1.0/14 1.0 (#18)
H1.0/16
H1.5/14 1.5 (#16)
H1.5/16
*1. This represents a typical model. Actually, colored codes and other information is added.
*2.
Although wires exceeding 2.0 mm
2
are available for AWG14, they cannot be used for the screwless
clamping terminal block.
When you use any ferrules other than those in the above table, crimp them to the twisted wires so
that the following processed dimensions are achieved.
8 to 10 mm
2.4 mm max.
(Terminals other than ground terminals)
2.7 mm max.
(Ground terminals)
1.6 mm max.
(Terminals other than ground terminals)
2.0 mm max.
(Ground terminals)
l
Using Twisted or Solid Wires
If you use twisted wires or solid wires, use the following table to determine the correct wire specifi-
cations.
5 Installation and Wiring
5-43
NX-series NX502 CPU Unit Hardware User's Manual (W629)
5-4 Wiring
5
5-4-8 Wiring to the CPU Unit Terminal Block