5 - 49
5 Setup and Wiring
Vision System FH/FZ5 series Hardware Setup Manual (Z366)
5-8 Installation in a Control Panel
5
5-8-4 FZ5 Series
Precautions for Correct Use
Ambient Temperature
Install and store the product in a location that meets the following conditions:
Surrounding temperature of 0 to 50°C (-20 to +65°C in storage)
Relative humidity of between 35 to 85%RH
Do not let the ambient temperature exceed 50°C (122°F).
Provide a forced-air fan cooling or air conditio
ning if the ambient temperature is near 50°C
(122°F) so that the ambient temperature never exceeds 50°C (122°F).
For good ventilation, provide a clearance of 50
mm or more above the Sensor Controller
away from other devices in the normal floor mounting. For the back side, 10 mm or more.
These clearances are also required when mounting multiple sensor controllers side by side.
For the back mounting, the back-side clearance of 15 mm is nor required. However, if the
adjacent devices do not generate heat, provide at least 50 mm of clearance from the top of
the Controller.
5-8-4 FZ5 Series