Event code
Event
name
Meaning Assumed cause
Level
Reference
M
a
j
P
rt
M
i
n
O
b
s
I
n
f
o
10400000 hex Analog Unit
Calibration
Parameter
Error
An error occurred for
the calibration data
in the Analog Unit.
The power supply to the Ana-
log Unit was turned OFF or
Support Software communi-
cations were disconnected
while writing the calibration
values to the Analog Unit.
¡
page
9 - 15
10410000 hex Control Pa-
rameter Er-
ror in Mas-
ter
An error occurred in
the control parame-
ters that are saved in
the master.
For the NX bus of CPU Units
The power supply to the CPU
Unit was turned OFF while
writing the Unit operation set-
tings was in progress. Or
there is an error in the area of
the non-volatile memory in
the CPU Unit in which the
Unit operation settings for the
NX Unit are saved.
For Communications Coupler
Units
The power supply to the
Communications Coupler
Unit was turned OFF while
writing the Unit operation set-
tings was in progress. Or
there is an error in the area of
the non-volatile memory in
the Communications Coupler
Unit in which the Unit opera-
tion settings for the NX Unit
are saved.
¡
page
9 - 16
10440000 hex Unit Cali-
bration V
al-
ue Error
There is an error in
the area in which the
Unit calibration val-
ues are saved.
There is an error in the area
of the non-volatile memory in
which the Unit calibration val-
ues are saved.
¡
page
9 - 17
9 Troubleshooting
9 - 7
NX-series Analog I/O Units Users Manual for High-speed Analog Input Units (W592)
9-3 Checking for Errors and Troubleshooting on the Support Software
9
9-3-3 Event Codes and Corrections for Errors

Table of Contents