1-3
Model
This section describes the model notation and model list of the High-speed Analog Input Units.
1-3-1
Model Notation
The model numbers of the High-speed Analog Input Units are assigned based on the following rules.
NX -£ £ £ £ £ £
Number of analog input points
4: 4 points
Unit type
HAD:
Other specification
Refer to
Other Specifications
below.
High-speed analog input
Other Specifications
Num-
ber
Analog input section
Trigger input
section
I/O re-
freshing
method
Input range Resolution
Input
method
Conver-
sion time
Num-
ber
of
point
s
Internal
I/O
com-
mon
01
• -10 to 10 V
• -5 to 5 V
• 0 to 10 V
• 0 to 5 V
• 1 to 5 V
• 0 to 20 mA
• 4 to 20 mA
• Input range of -10 to 10 V
or -5 to 5 V
1/64000 (full scale)
• Other input ranges
1/32000 (full scale)
Differential
input
5 µs per
channel
4
point
s
NPN Synchro-
nous I/O
refreshing
02 4
point
s
PNP
Refer to Section 5 I/O Refreshing on page 5 - 1 for details on the I/O refreshing method.
1-3-2
Model List
The following table lists the different models of the High-speed Analog Input Units.
For detailed specifications for each Unit, refer to A-1-2 High-speed Analog Input Units on page
A - 3.
1 Features and System Configuration
1 - 9
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
1-3 Model
1
1-3-1 Model Notation

Table of Contents

Other manuals for Omron SYSMAC NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC NX series and is the answer not in the manual?

Omron SYSMAC NX series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC NX series
CategoryController
LanguageEnglish

Related product manuals