Event name Unit Calibration Value Error Event code 10440000 hex
Meaning There is an error in the area in which the Unit calibration values are saved.
Source Depends on where the Support
Software is connected and the
system configuration.
Source details NX Unit Detection tim-
ing
When power is
turned ON to
the NX Unit
Error attrib-
utes
Level Minor fault Log category System
Recovery ---
Effects User program Continues. Operation The NX Unit will continue to operate.
Input data: Updating input values stops.
System-de-
fined varia-
bles
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
There is an error in the area of
the non-volatile memory in which
the Unit calibration values are
saved.
Cycle the power to the NX Unit
and see if this clears the error
.
If the error occurs again even af-
ter you make the above correc-
tion, replace the NX Unit.
None
Attached in-
formation
None
Precautions/
Remarks
None
9 Troubleshooting
9 - 17
NX-series Analog I/O Units Users Manual for High-speed Analog Input Units (W592)
9-3 Checking for Errors and Troubleshooting on the Support Software
9
9-3-4 Meaning of Error

Table of Contents

Other manuals for Omron SYSMAC NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC NX series and is the answer not in the manual?

Omron SYSMAC NX series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC NX series
CategoryController
LanguageEnglish

Related product manuals