• Table 5-15 (page 5-28) Threshold Values for Oracle Exadata Database Machine
X3-2 Full Rack with Single-phase, High-voltage PDU
• Table 5-16 (page 5-28)
Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with
Three-phase, High-voltage PDU
Table 5-13 (page 5-27) lists the threshold values for Oracle Exadata Database
Machine X3-2 Full Rack using a single-phase, low-voltage PDU.
Table 5-13 Threshold Values for Oracle Exadata Database Machine X3-2 Full
Rack with Single-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 20 24
A Module 1, phase
2
0 14 18
A Module 1, phase
3
0 19 24
B Module 1, phase
1
0 19 24
B Module 1, phase
2
0 14 18
B Module 1, phase
3
0 20 24
Table 5-14 (page 5-27) lists the threshold values for Oracle Exadata Database
Machine X3-2 Full Rack using a three-phase, low-voltage PDU.
Table 5-14 Threshold Values for Oracle Exadata Database Machine X3-2 Full
Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 30 38
A and B Module 1, phase
2
0 32 40
A and B Module 1, phase
3
0 30 38
Table 5-15 (page 5-28) lists the threshold values for Oracle Exadata Database
Machine X3-2 Full Rack using a single-phase, high-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-27