Table 5-15 Threshold Values for Oracle Exadata Database Machine X3-2 Full
Rack with Single-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 18 23
A Module 1, phase
2
0 13 17
A Module 1, phase
3
0 18 22
B Module 1, phase
1
0 18 22
B Module 1, phase
2
0 13 17
B Module 1, phase
3
0 18 23
Table 5-16 (page 5-28) lists the threshold values for Oracle Exadata Database
Machine X3-2 Full Rack using a three-phase, high-voltage PDU.
Table 5-16 Threshold Values for Oracle Exadata Database Machine X3-2 Full
Rack with Three-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 17 21
A and B Module 1, phase
2
0 17 21
A and B Module 1, phase
3
0 15 19
5.3.1.3.2 PDU Thresholds for Oracle Exadata Database Machine X3-2 Half Rack
The following tables list the threshold values for Oracle Exadata Database Machine
X3-2 Half Rack:
• Table 5-17 (page 5-29) Threshold Values for Oracle Exadata Database Machine
X3-2 Half Rack with Single-phase, Low-voltage PDU
• Table 5-18 (page 5-29) Threshold Values for Oracle Exadata Database Machine
X3-2 Half Rack with Three-phase, Low-voltage PDU
• Table 5-19 (page 5-29) Threshold Values for Oracle Exadata Database Machine
X3-2 Half Rack with Single-phase, High-voltage PDU
• Table 5-20 (page 5-30) Threshold Values for Oracle Exadata Database Machine
X3-2 Half Rack with Three-phase, High-voltage PDU
Table 5-17 (page 5-29) lists the threshold values for Oracle Exadata Database
Machine X3-2 Half Rack using a single-phase, low-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-28