6-6 Programming Your Application
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
ENERGY SAVING
F VF
When set TRUE, the demanded volts are reduced
to minimise energy consumption if the drive is
operating in a steady state at light load.
0=FALSE
1=TRUE
0
MOTOR
CURRENT
M SV
This parameter contains the motor nameplate full-
load line current
0.01 to 999.99A product
code
dependent
MOTOR POLES
M SV
This parameter contains the number of motor
poles, as supplied on the motor nameplate
2=2 pole
4=4 pole
6=6 pole
8=8 pole
10=10 pole
12=12 pole
1
MOTOR
VOLTAGE
M
This parameter contains the motor nameplate
voltage at base frequency
0.0 to 575.0V product
code
dependent
MAG CURRENT
M
This parameter contains the motor model no-load
line current as determined by the Autotune, or
taken from the motor nameplate
0.01 to 999.99 A product
code
dependent
POWER
M SV
This parameter contains the motor nameplate
power.
0.00 to 355.00kW product
code
dependent
MOTOR
CONNECTION
M SV
This parameter contains the motor nameplate
connection.
0= DELTA
1= STAR
1
STATOR RES
F M SV
This parameter contains the motor model per-
phase stator resistance as determined by Autotune.
0.0000 to
250.0000
product
code
dependent
LEAKAGE INDUC
F M SV
This parameter contains the motor model per-
phase leakage inductance as determined by
Autotune.
0.00 to 300.00mH product
code
dependent
MUTUAL INDUC
F M SV
This parameter contains the motor model per-
phase mutual inductance as determined by
Autotune.
0.00 to 3000.00mH product
code
dependent
ROTOR TIME
CONST
F M SV
This parameter contains the motor model rotor
time constant as determined by Autotune.
10.00 to 3000.00ms product
code
dependent
AUTOTUNE
MODE
SV
Selects the Autotune operating mode. 0= STATIONARY
1= ROTATING
0
AUTOTUNE
ENABLE
SV
Determines whether the Autotune sequence is
operational or not. The Autotune sequence is
operational when set to TRUE and the drive is run
0=FALSE
1=TRUE
0
CURRENT LIMIT
F
This parameter sets the level of motor current, as a
% of MOTOR CURRENT (
S
CL10) at which the drive
begins to take current limit action.
0.00 to 300.00% 300.00%
POS TORQUE
LIMIT
F
This parameter sets the maximum allowed level of
positive motor torque.
-500.0 to 500.0% 200.0%
NEG TORQUE
LIMIT
F
This parameter sets the maximum allowed level of
negative motor torque.
-500.0 to 500.0% -200.0%
STALL TRIP TYPE
F
This parameter determines whether the stall trip
operates on motor torque or motor current.
FALSE = TORQUE, TRUE = CURRENT
0= FALSE
1= TRUE
1
SPEED PROP
GAIN
F M SV
Sets the proportional gain of the loop.
Speed error (revolutions per second) x proportional
gain = torque percent.
0.00 to 300.00 product
code
dependent