Programming Your Application 6-7
650V AC Drive
MMI Parameters Table
SPEED INT TIME
F M SV
This is the integral time constant of the speed loop.
A speed error which causes the proportional term
to produce a torque demand T, will cause the
integral term to also ramp up to a torque demand
T after a time equal to “speed int time”.
1 to 15000ms product
code
dependent
SPEED POS LIMIT
F SV
This sets the upper limit of the speed demand. -110.00 to 110.00% 110.00%
SPEED NEG LIMIT
F SV
This sets the lower limit of the speed demand. -110.00 to 110.00% -110.00%
DIN 1 INVERT Inverts the value of the signal, TRUE or FALSE. 0= FALSE
1= TRUE
0
DIN 2 INVERT As
S
IP01 As
S
IP01 0
DIN 3 INVERT As
S
IP01 As
S
IP01 0
DIN 4 INVERT As
S
IP01 As
S
IP01 0
DIN 5 INVERT As
S
IP01 As
S
IP01 1
DIN 6 INVERT As
S
IP01 As
S
IP01 0
DIN 7 INVERT As
S
IP01 As
S
IP01 0
AIN 1 SCALE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
-300.0 to 300.0% 100.0%
AIN 1 OFFSET -300.0 to 300.0% 0.0%
AIN 1 TYPE 0= 0-10V
1= 0-5V
0
AIN 2 SCALE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
-300.0 to 300.0% 100.0%
AIN 2 OFFSET -300.0 to 300.0% 0.0%
AIN 2 TYPE 0= 0-10V
1= 0-5V
2= 0-20mA
3= 4-20mA
3
DIN 1 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
0
DIN 2 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
0
F
The TRUE or FALSE input (after any inversion)
1=TRUE
DIN 4 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
0
DIN 5 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
0
DIN 6 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
0
DIN 7 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
0
AIN 1 VALUE
F
The input reading with scaling and offset applied
.x%
—.x%
AIN 2 VALUE
F
The input reading with scaling and offset applied
.x%
—.x%