56 57
Wiring diagrams
for thermocouple input
TC temperature sensor input with
internal cold junction compensation
(CJC). CJC connector including Pt100
element type 5911 is used.
Please notice terminal no. 41 and 42
must be short circuited with a wire.
TC temperature sensor input with
external cold junction compensation
(CJC). A Pt100 element is used in
the junction between the TC and the
copper terminal.
TC temperature sensor input without
cold junction compensation.
For constant temperature in the
junction between the TC and the
copper terminal.
Differential input for TC temperature
sensors.
Cold junction (CJC) is compensated
by the TC.
Wiring of power supply, analogue output
and relay outputs.