Chapter 5 Trigger    RIGOL 
MSO4000/DS4000 User’s Guide  5-17 
2.  Adjust the trigger level 
In runt trigger, you need to set the trigger level upper limit and trigger level 
lower limit which correspond to the trigger labels 
 and   respectively. 
 
  Select the trigger level to be adjusted 
Press Vertical and turn the multi-function knob   to select the desired 
vertical window type (different type of vertical window corresponds to 
different trigger level adjustment mode). You can also press Vertical 
continuously to switch the current vertical window type.  
―  : only adjust the upper limit of the trigger level and the lower 
limit remains unchanged.  
― 
: only adjust the lower limit of the trigger level and the upper 
limit remains unchanged. 
― 
: adjust the upper limit and lower limit of the trigger level at the 
same time and the trigger level difference (namely the difference 
between the upper limit and lower limit) remains unchanged.  
 
Here, in runt trigger, pressing TRIGGER    LEVEL can quickly switch the 
current vertical window type.  
 
  Adjust the trigger level 
Turn Trigger    LEVEL to adjust the corresponding trigger level 
(determined by the type of the vertical window currently selected).  
 
During the adjustment, two trigger level lines (orange dotted lines) appear 
on the screen and move up and down with the variation of the trigger level. 
At the same time, the trigger level information (as shown in the figure 
below, Up Level denotes the upper limit of the trigger level and Low Level 
denotes the lower limit of the trigger level) pops up at the lower-left side of 
the screen in real-time. The trigger level lines and trigger level information 
at the lower-left side of the screen disappear about 2 s later after you stop 
modifying the trigger level. The current trigger level difference is displayed 
at the upper-right side of the screen. 
 
 
www.calcert.com sales@calcert.com1.800.544.2843
0
5
10
15
20
25
30