Command Answer Description
S01; Select unit 1
LRP?0; 0,2,"C500-K501",1,"SWTTSG"CRLF Package 0 is C500-K501, it is li-
censed with code SWTTSG. There
are 2 packages installed.
LRP?1; 1,2,"L900-500",1,"IAHUZA"CRLF Package 1 is L900-500, it is licensed
with code IAHUZA.
LRP,"L900-500",0; 0 CRLF Unlicense package L900-500.
LRP?1; 1,2,"L900-500",0,""CRLF Package 1 is L900-500, it is not li-
censed.
LRP,"L900-500",1,"IAHUZA"; 0 CRLF License package L900-500 with
code IAHUZA.
LRP?1; 1,2,"L900-500",1,"IAHUZA"CRLF Package 1 is L900-500, it is licensed
with code IAHUZA.
21.3.33 LWT: Legacy Span Calibration
Calibrate the span of the scale. Due to the removal of the normal/direct calibration mode, this command only
supports normal span calibration. For mV/V calibration see the new LWN; command (see Section 21.3.31).
General
No. of parameters 0
Save changes With TDD1
Increment Trade Counter Yes
The calibration process takes some time to complete. As a result it is necessary to monitor the calibration
process to determine when it is finished. To do this, issue a LWT? query. Shown below is a list of the possible
calibration status responses. Refer to the calibration status table for the LWN command in Section 21.3.31.
Example
Command Answer Description
S01; Select unit 1
LWT; 0 CRLF Start span calibration
LWT?; 1 CRLF Query status of the span calibration process
LWT?; 1 CRLF Still busy
LWT?; 0 CRLF Span calibration finished
TDD1; 0 CRLF Save setting
21.3.34 MBS: Modbus settings
Set parameters for Modbus.
General
No. of parameters 2
Save changes With TDD1
Increment Trade Counter -
Parameter Details
Parameter Description Range Default
1 Modbus 32bit value endian 0 = Big endian
1 = Little endian
0 (Big endian)
2 Modbus TCP listening port 502 .. 65535 502
Example