Controller functions
RES-445 Page 63
Part 3 of 3:
NOTE: The specified error messages are initially output as warnings (actual value output jumps back and forth between two values;
alarm relay is open). When the "START" signal is activated, the warning changes to a fault
(actual value output no longer jumps back and forth, see bold italic values; alarm relay is closed).
Action if machine
already operating,
HS band not chang.
---
---
---
Action
if machine started
for first time
Fault area
,
check configuration
Fault area
,
check configuration
Fault area
,
check configuration
Cause
I
R
signal incorrect,
calibration not possible
U
R
signal incorrect,
calibration not possible
U
R
and I
R
signals incorrect,
calibration not possible
Temperature fluctuates,
calibration not possible
Ext. calibration
temperature too high,
Ext. calibration
temperature fluctuates
STATUS
of alarm relay
(factory set.)
Warning:
Open
Fault:
Closed
(voltage value
at actual
value output
then no longer
changes)
Temp.
500°C
[°C]
333
500
366
500
400
500
433
500
Temp.
300°C
[°C]
200
300
220
300
240
300
260
300
Act. value
output;
Voltage [V]
6,66
10
7,33
10
8,00
10
8,66
10
Error
code
111
112
113
114
115
116
10
11
12
13