120 CompTrol Interface V4.0.x | Issue 21-05-2021 | 1000932
Appendix II: Start-up Report
Table 1: Set signal ranges on both Interface PCBs
(check box as applicable)
Interface 1
S2-3 S2-4
0 to 2.7 V, without signal overlap
0 to 10.8 mA, without signal overlap
0 to 12.6 mA, without signal overlap
2.7 to 5 V, without signal overlap
10.8 to 20 mA, without signal overlap
12.6 to 20 mA, without signal overlap
0 to 2.9 V, with signal overlap
0 to 11.6 mA, with signal overlap
0 to 13.3 mA, with signal overlap
2.5 to 5 V, with signal overlap
10 to 20 mA, with signal overlap
12 to 20 mA, with signal overlap
Interface 2
S2-3 S2-4
0 to 2.7 V, without signal overlap
0 to 10.8 mA, without signal overlap
0 to 12.6 mA, without signal overlap
2.7 to 5 V, without signal overlap
10.8 to 20 mA, without signal overlap
12.6 to 20 mA, without signal overlap
0 to 2.9 V, with signal overlap
0 to 11.6 mA, with signal overlap
0 to 13.3 mA, with signal overlap
2.5 to 5 V, with signal overlap
10 to 20 mA, with signal overlap
12 to 20 mA, with signal overlap
5 to 10 V, with signal overlap
Activated
Signal range Activated Description
0 to 5.4 V, without signal overlap
OFF OFF A
0 to 5.4 V, without signal overlap
ON ON B
5.4 to 10 V, without signal overlap
OFF ON C
0 to 5.8 V, with signal overlap
ON D
5 to 10 V, with signal overlap
OFFOFF A
ONON
0 to 5.8 V, with signal overlap
CONOFF
Signal range Description
D
ONON
ON
5.4 to 10 V, without signal overlap
B