Product Specifications
Samsung Electronics 21
Standard type (AMSSSJXVSSS)
System Model
Capacity of Single Unit (HP)
Capa Code
No. of Modules 8HP
10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP
8HP
AM080JXVAGH 1 1
10HP AM100JXVAGH 1 1
12HP AM120JXVAGH 1 1
14HP AM140JXVAGH 1 1
16HP AM160JXVAGH 1 1
18HP AM180JXVAGH 1 1
20HP AM200JXVAGH 1 1
22HP AM220JXVAGH 1 1
24HP AM240HXVAGH 1 1
26HP AM260HXVAGH 1 1
28HP AM280JXVAGH1 2 1
1
30HP AM300JXVAGH1 2 1
1
32HP AM320JXVAGH1 2 1
1
34HP AM340JXVAGH1 2 1 1
36HP AM360JXVAGH1 2 1 1
38HP AM380JXVAGH1 2 1 1
40HP AM400JXVAGH1 2
1 1
42HP AM420JXVAGH1 2 1 1
44HP AM440JXVAGH1 2 2
46HP AM460JXVAGH1 3
2 1
48HP AM480JXVAGH1 3
1 1 1
50HP AM500JXVAGH1 3
1 1 1
52HP AM520JXVAGH1 3
1 1
1
54HP AM540JXVAGH1 3
1 1 1
56HP AM560JXVAGH1 3
1 2
58HP AM580JXVAGH1 3
1 2
60HP AM600JXVAGH1 3
1 2
62HP AM620JXVAGH1 3
1
2
64HP AM640JXVAGH1 3
1
2
66HP AM660JXVAGH1 3 3
68HP AM680JXVAGH1 4
2
2
70HP AM700JXVAGH1 4
1 1
2
72HP AM720JXVAGH1 4
1 1
2
74HP AM740JXVAGH1 4
1 1
2
76HP AM760JXVAGH1 4
1 1
2
78HP AM780JXVAGH1 4
1
3
80HP AM800JXVAGH1 4
1
3
Make sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and
heating capacity of the indoor unit may decrease.
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 x ∑ (Outdoor unit capacity) ≤ Total capacity of the connected indoor unit ≤ 1.3 x ∑ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit.
Maximum quantity of connectable indoor unit is set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can
be Assigned from 0~63.
If the indoor unit address was assigned from 64~79, E201 error will occur.
M* : Outdoor Unit Combination has been added.
In case of combining modules more than 90HP, please consult the manufacturer when connecting the indoor unit and deciding
on piping length in accordance with design of the building.
2-2 Model names of Indoor/Outdoor Unit (cont.)
2-2-1 Outdoor unit combination (cont.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM080FX A Series and is the answer not in the manual?

Samsung AM080FX A Series Specifications

General IconGeneral
BrandSamsung
ModelAM080FX A Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals