Piping Diagram
Samsung Electronics 330
Safety Start Normal Start
Purpose
Stable start-up in a low-temperature section with overload
Concept
Compressors start in sequential order to ensure stable operation if the indoor unit operation ratio is low or there is an overload.
Control specifications in detail
- Condition(s) required to enter Normal Start mode : None of the conditions required to enter Quick Start mode are satisfied.
- In Normal Start mode, compressors are controlled as shown below.
(See the chart below for conditions required to complete specific steps)
- Condition(s) required to enter Normal Operation mode : [ A or B ]
A. DSH > 10 K B. Max (Tdis, Ttop) ≥ 30
- Cold Operation mode will activate if none of the conditions required to enter Normal Operation mode are satisfied.
- In Cold Operation mode, the compressor frequency increase speed is restricted to 1Hz per 30 sec.
- Condition(s) required to close Cold Operation mode: [ A or B ]
A. A maximum of 30 min has elapsed B. DSH > 15 K
7-3 Functions (cont.)
7-3-2-2 Start-up modes (cont.)
7-3-2 Control (cont.)