Piping Diagram
Cooling operation
▪ Purpose
Enable cooling in the entire target space.
▪ Control specifications in detail
- Condition(s) required to enter Quick Start mode: [ A & B ]
▪ Refrigerant Flow
Heat pump
Actuator Abbrev. - Normal Cooling
Compressor COMP
Operation
Target low pressure control
(default : 8kgf/cm2,g)
Range 14~140Hz
Outdoor Fan Motor OFM
Operation
Target high pressure control
(default : 25kgf/cm2,g)
Range 0-39step (0-1300rpm)
Electronic Expansion Valve
– Main (Main EEV)
E_M
Operation Full Open
Range 2000step
Electronic Expansion Valve
– EVI (EVI EEV)
E_EVI
Operation
*Subcooling control
(default: SC 20 K)
Range 0-480step
Solenoid Valve - 4way V_4W Operation Off
Solenoid Valve – EVI Bypass V_EB Operation
On (Open): *T_a > 38℃ or 50Hz ↓
Off (Close): T_a < 36℃↓ and 70Hz ↑
Solenoid Valve – EVI V_EVI Operation On (Open)
Solenoid Valve – Hot Gas Bypass V_HG Operation Off (Close)
Solenoid Valve – Accumulator Oil Return V_AR Operation On (Open)
Solenoid Valve – Hot Gas Bypass 2 (HR Only) V_HG2 Operation On (Open)
Solenoid Valve – Main EEV (HR Only) V_ME Operation On (Open)
Solenoid Valve – Main Cooling (HR Only) V_MC Operation Off (Close)
↑
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
Outdoor Heat Exchanger (OHX)
High Temperature & pressure Gas
High Temperature & pressure Liquid
Low Temperature & pressure Gas
Low Temperature & pressure Liquid
COOL
FAN ON
↑
↑
↑
↑ ↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
Ball Valve -
Gas pipe (BV_G)
Outdoor Fan Motor 1
(OFM1)
Outdoor Fan Motor 2
(OFM2)
Thermistor - Ambient (T_A)
Thermistor -
Cond Out (T_CO)
Heat Exchanger - Main (HX_M)
Thermistor - Suction pipe (T_S)
Check Valve -
EEV Bypass (CV_EB)
Electronic Expansion
Valve - Main (E_M)
IPM Cooler 1
(IPMC1)
IPM Cooler 2
(IPMC2)
Heat Exchanger -
Intercooler (HX_IC)
Thermistor -
EVI In (T_EI)
Thermistor -
Liquid pipe (T_L)
Electronic
Expansion
Valve -
EVI (E_EVI)
Thermistor -
EVI Out (T_EO)
Solenoid Valve -
EVI Bypass
(V_EB)
Ball Valve -
Liquid pipe (BV_L)
Solenoid Valve -
Accumulator oil Return (V_AR)
Pressure Sensor -
Low (PS_L)
Solenoid Valve -
Hot Gas bypass (V_HG)
(V_EVI2)
Solenoid
Valve -
EVI 1(V_EVI1)
Compressor 1
(COMP1)
(COMP2)
(T_D2)
(T_CT2)
Thermistor -
Discharge
pipe 1 (T_D1)
(PW_H2)
(OS2)
(CV_D2)
Oil Separator 1
(OS1)
Pressure Sensor -
High (PS_H)
Solenoid Valve - 4Way (V_4W)
Pressure
Switch -
High 1
(PW_H1)
Thermistor -
Compressor
Top 1
(T_CT1)
Check Valve -
Discharge 1
(CV_D1)
Accumulator
(AC)
↑
↑ ↑
COOL
FAN ON
COOL
FAN ON
OFF
FAN OFF
COOL
FAN ON
OFF
FAN OFF
7-3 Functions (cont.)
7-3-2-3 Normal operation modes
7-3-2 Control (cont.)