EasyManua.ls Logo

Samsung AM080FX A Series - Page 356

Samsung AM080FX A Series
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Samsung Electronics 375
Piping Diagram
High-head condition setting
Purpose
Secure performance and reliability when using units installed under a high-head condition.
Concept
- Control of the compressor frequency, outdoor fans, EEV, and valves is optimized to facilitate the circulation of
refrigerant in any head condition.
Control specifications in detail
- In Type 1 heating mode, the initial EEV opening degree increases.
The compressor frequency increase speed decreases if the low pressure is low
(see "Main EEV control" for details on EEV control).
- In Type 2 heating mode, the initial EEV opening degree decreases.
The compressor frequency increase speed decreases if the low pressure is low
(see "Main EEV control" for details on EEV control).
- In Type 2 cooling mode, the target high pressure for outdoor fans increases to 28kgf/cm2,g.
(see "Fan control" for details on controlling outdoor fans).
- In Type 1 and 2 cooling modes, EVI bypass mode turns on (see “EVI EEV control“ for details).
Notes
- Incorrect settings may damage the system.
Input unit Seg1 Seg2 Seg3 Seg4 Silent mode for night - time
Main 0 8
0 0 Disabled (default)
0 1
Level 1 of Type1
(When outdoor unit is located 40~80m
above the indoor unit)
0 2
Level 2 of Type 1
(When outdoor unit is located over 80m
above the indoor unit)
0 3
Type 2
(When indoor unit is over 30m above the outdoor unit)
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)

Table of Contents

Related product manuals