Samsung Electronics 388
Key Options
※ 3. Quantity of indoor unit
: To set the quantity of connected indoor unit. (Main outdoor unit only)
- If the quantity of IDU which is communicating with outdoor unit is different error will be displayed.(E201)
IDU Quantity Ex) IDU 6ea Ex) IDU 26ea
10-digit
1-digit
0 2
2 6
※ 4. Quantity of MCU
: To set the quantity of connected MCU. (Main outdoor unit only)
- If the quantity of MCU which is communicating with outdoor unit is different error will be displayed.(E214)
Setting Ex) MCU 2ea Ex) MCU 12ea
MCU Quantity
1~F
(A=10, B=11, ~, F=15)
2 C
8-3 Outdoor unit option switch settings (cont.)