Key Options
Samsung Electronics 397
8-4 How to check the view mode using a tact switch (cont.)
AM140/160/180/200/220/240/260/280/300KXVSSSS
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency
operation for
compressor
malfunction
Individual 0 0
0 0 Disabled (Factory default)
E560 will occur when all
the compressors are set as
malfunction state.
0 1
Set compressor 1 as
malfunction state
0 2
Set compressor 2 as
malfunction state
Cooling capacity
correction
Main 0 1
0 0 7~9
Targeted evaporation
temperature [°C]
(When low temperature
value is set, discharged air
temperature of the indoor unit
will decrease)
0 1 5~7(Factory default)
0 2 9~11
0 3 10~12
0 4 11~13
0 5 12~14
0 6 13~15
Capcity
correction for
heating
Main 0 2
0 0 3 0 (Factory default)
Targeted high pressure [MPa]
(When low pressure value
is set, discharged air
temperature of the indoor
unit will decrease)
0 1 2 5
0 2 2 6
0 3 2 7
0 4 2 8
0 5 2 9
0 6 3 1
0 7 3 2
0 8 3 3
Current
restriction rate
Individual 0 3
0 0 100% (Factory default)
When restriction option is
set, cooling and heating
performance may decrease.
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0 7 65 %
0 8 60 %
0 9 55 %
1 0 50 %
1 1 No restriction
Oil collection
interval
Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
0 0 Factory default
0 1
Apply setting when the
product is being installed in
humid area such as near river
or lake
Fan speed
correction for
outdoor unit
Individual 0 6
0 0 Factory default
0 1 Increase fan speed
Increase the outdoor unit's fan
speed to maximum value.