Key Options
8-4 How to check the view mode using a tact switch (cont.)
AM140/160/180/200/220/240/260/280/300KXVSSSS
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
Enables the silent mode
for night-time (It operates
automatically depending on
the temperature )
However, if the external
contact interface module
(MIM-B14) is used, entering
the silent mode is available
with contact signal
0 1 LEVEL 1 / Auto
0 2 LEVEL 2 / Auto
0 3 LEVEL 3 / Auto
0 4 LEVEL 1 / External contact
0 5 LEVEL 2 / External contact
0 6 LEVEL 3 / External contact
High-head
condition setting
Main 0 8
0 0 Disabled (Factory default)
0 1
Level 1 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is located
40~80m above the indoor
unit
0 2
Level 2 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is located
over 80m above the indoor
unit
0 3
Height difference type 2
(Outdoor unit is lower than
indoor unit)
When indoor unit is over 30 m
above the outdoor unit
Long-pipng
condition
setting
(Setting
is unnecessary
if high-head
condition is set)
Main 0 9
0 0 Disabled (Factory default)
0 1 LEVEL 1
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170m
0 2 LEVEL 2
When equivalent length of
farthest indoor unit from the
outdoor unit is over 170m
Energy control
Operaton
Individual 1 0
0 0 Basic (Factory default) Energy control option
of designated operation
sequence.
Operating in energy
saving mode, capacity
might decrease compared
to normal operation mode.
0 1 Energy saving
0 2 Power
Rotation defrost
(HR only)
Main 1 1
0 0 Disabled (Factory default)
0 1 Enabled
When enabled, continuous
heating operation is possible
but heating performance
will decrease during rotation
defrost operation.
Expand
operational
temperature
range for cooling
operation
(HR only)
Individual 1 2
0 0 Disabled (Factory default)
0 1 Enabled
When enabled, continuous
cooling operation is possible
even in low temperature
condition up to -15°C, but
noise of the MCU will increase.
Channel address Main 1 3
A U
Automatic setting
(Factory default)
Address for classifying the
product from upper level
controller. (DMS, S-NET 3, etc )
0 ~ 15
Manual setting for channel
0~15
Snow
accumulation
prevention
control
Main 1 4
0 0 Enabled (Factory default)
During snow accmulation , the
fan may spin even when the
unit is not in operation.
0 1 Disabled
Unused option Main 1 5 0 0 Unused option Unused option by this model.
Unused option Main 1 6 0 0 Unused option Unused option by this model.