EasyManua.ls Logo

Samsung EHS AE080BXYDEG/EU - Page 187

Samsung EHS AE080BXYDEG/EU
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11. Trouble shooting
Installer reference guide / Mono tank integrated type 186
Fault Possible cause Remedy
The pump is blocked
If the unit has been powered off for a long
time, lime might block the rotor of the pump.
When a locked rotor occurs for 3 seconds, a
locked rotor fault is reported.
The pump stops working and the
indicator(Both MAX & PWM LED) flashes 5
times.
Every 8 seconds, the pump tries to re-start.
If the fault is not eliminated, after 5 failed
attempts the pump will no longer re-start.
The indicator continues to flash. The pump
requires a power reset.
If the fault continues, disassemble the pump
and clean and free the locked rotor.
Flow error E911 is displayed.
The pump is blocked or there is not sufficient
voltage towards the pump.
The pump is making
noise (cavitation)
There is air in the system.
Purge air from the system by opening the
automatic air vent.
The water pressure at the pump inlet is
too low.
Check and make sure that
The water pressure is >1 bar.
The water pressure sensor is not broken.
The expansion vessel is not broken.
The valve (if equipped) of the water circuit
towards the expansion vessel is open.
The pre-pressure setting of the expansion
vessel is correct.
The strainer is clean.
The pressure relief
valve opens
The expansion vessel is broken or sized too
small for the total volume.
Replace the expansion vessel or add another
after determining the needed expansion size.
The valve (if equipped) of the water circuit
towards the expansion vessel is closed.
Open the valve.
The water volume in the installation is too
high.
Make sure that the water volume in the
installation is below the maximum allowed
value.
The water circuit head pressure is too high.
The pressure relief valve is 3 bar. Check the
water circuit head pressure.
The water pressure
relief valve leaks
Dirt is blocking the water pressure relief valve
outlet.
Check that the pressure relief valve is
working properly by turning the valve on or
off.
If the water keeps running out of the unit,
close both the water inlet and outlet shut-off
valves first and then if broken, replace it. The
system must have a good working pressure
relief valve for operating safely.

Table of Contents

Related product manuals