Denite Time 1 Min. TimeThis is the time delay (in seconds) after which the Denite
Time 1 element trips. (Range: 0.000-600.000; Step: 0.001)
Denite Time 2 Min. TripThis is the current (in primary amperes) at which the
Denite Time 2 element picks up. (Range: 6-16,000; Step: 1) The stated maximum is
for 15-kV IntelliRupter fault interrupters; 27-kV and 38-kV are limited to 12,500 amps
maximum.
Denite Time 2 Min. TimeThis is the time delay (in seconds) after which the Denite
Time 2 element trips. (Range: 0.000-600.000; Step: 0.001)
Sensitive Earth
The Sensitive Earth element trips the IntelliRupter fault interrupter if the computed
residual of the three-phase elements exceeds the pickup value for the time value set by
the inverse curve or the denite time delay.
Sensitive Earth Check boxCheck to enable this element.
Inverse SegmentSelect from the drop-down list of inverse curve names or select the
None option. Only the Denite Time settings will be used when the None option is
selected.
Min. TripThis is the current (in primary amperes) at which the inverse curve begins
timing. (Range: 3-16,000; Step: 1) The stated maximum is for 15-kV IntelliRupter fault
interrupters; 27-kV and 38-kV are limited to 12,500 amps maximum.
Min. TimeThis is the time (in seconds) dening the fastest response of the inverse
curve portion of the TCC curve. (Range: 1.000-6000.000; Step: 0.001)
Time MultThis is the time modier for the inverse curve. (Range: 0.01-15.00; Step: 0.01)
Time AdderThis is the time modier for the inverse curve. (Range: -10.000-100.000;
Step: 0.001)
Low Cutoff—This is the current (in primary amperes) at which the TCC curve begins
timing. (Range: 3-16,000; Step: 1) The stated maximum is for 15-kV IntelliRupter fault
interrupters; 27-kV and 38-kV are limited to 12,500 amps maximum.
ResetThe reset for the inverse curve is congurable for either the D/T (Denite Time) or
the T/A (Time Accumulation) mode. The Time Accumulation method times when current
is above the Minimum Trip value, and it holds the time value when current is below the
Minimum Trip value. The timer continues to count until either the SEF element trips
or the element does not pick up for the duration of the user-specied SEF Element Reset
Time parameter and the element resets. The Time Accumulation method is the default.
Reset TimeWhen the Denite Time reset mode is selected, enter the reset delay time
(in seconds). (Range: 0.000-6000.000; Step: 0.001)
Denite Time 1 Min. TripThis is the current (in primary amperes) at which the
Denite Time 1 element picks up. (Range: 3-16000; Step: 1) The stated maximum is
for 15-kV IntelliRupter fault interrupters; 27-kV and 38-kV are limited to 12,500 amps
maximum.
Denite Time 1 Min. TimeThis is the time delay (in seconds) after which the Denite
Time 1 element trips. (Range: 1.000-6000.000; Step: 0.001)
S&C Instruction Sheet 766-530 103
Protection Setup

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C IntelliRupter PulseCloser and is the answer not in the manual?

S&C IntelliRupter PulseCloser Specifications

General IconGeneral
BrandS&C
ModelIntelliRupter PulseCloser
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals