EasyManua.ls Logo

S&C IntelliRupter PulseCloser - Page 110

S&C IntelliRupter PulseCloser
181 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cold Load Pickup Activated
Select the Enabled mode to congure the Cold Load Pickup modier settings.
Max Modifier – Percent of Minimum Trip/Low Current Cutoff
Percent of the Min Trip/Low Current Cutoff setpoint at which timing is inhibited.
Pickup and timing above this level will follow the congured inverse characteristics.
(Range: 100%-500%; Step: 1%; Default: 200%)
T1—Start Applying Modifier after Outage
This is the duration of the power outage (in minutes) when the modier is applied at its
minimum value. (Range: 1-600; Step: 1; Default: 15)
T2—Ramp to Full Modifier Value after T1
This is the time after T1 (in minutes) when the modier has ramped up to its maximum
value. (Range: 0-600; Step: 1; Default: 15)
T3—Start Ramping Modifier Down after Return
This is the duration of power restoration (in minutes) when the modier is ramped down
from its maximum value. (Range: 0-600; Step: 1; Default: 15)
T4—Modifier Completely Off after T3
This is the time after T3 (in minutes) when the modier is removed at its minimum value.
(Range: 1-600; Step: 1; Default: 15)
Viable Voltage Setting
This is the percentage of system phase-to-phase voltage at which the Cold Load Pickup
Timer starts. (Range: 5%-95%; Step: 1%; Default: 90%)
Figure 60. The Setup>Protection>Cold Load Pickup screen.
110 S&C Instruction Sheet 766-530
Protection Setup

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Related product manuals