Normal State
The Normally Open state is for an IntelliRupter fault interrupter at the tie point between
two feeders. The Normally Closed state is for any other IntelliRupter fault interrupter on
the feeder. This parameter is not available when the Loop Restoration mode is disabled.
Protection
Choose the Voltage Trip or Sectionalizing element for triggering the Loop-Restoration
mode. The Voltage Trip element is usually selected. This parameter is only available
when the Closed Normal state and the Loop Restoration mode are enabled.
Good Frequency to Close
When the Yes option is chosen for the Good Frequency to Close mode, a Loop
Restoration Close command will be blocked if the frequency is below the active Under
Frequency Threshold for the congured Under Frequency Minimum Time to Detect
setpoint. When the No setting is chosen for the Good Frequency to Close mode, a Loop
Restoration Close command will not be blocked.
The Yes option is chosen for the Under Frequency Enabled setpoint on the
Setup>Protection>General Profiles>Voltage Frequency Sectionalizing>Frequency
Trip Section screen. The Loop Restoration mode must be manually enabled after the
Low-Frequency condition has cleared.
Loop Restoration Test Sequence Section
Closing Profile 1 and Closing Profile 2
The closing prole names are shown here for reference. They are congured on the
Setup>Protection>Closing Prole 1 or 2>Closing Prole 1 or 2>Current>Closing
Prole Main screen.
Add Test and Remove Test buttons
Select the number of loop-restoration tests to be performed. At least one test is always
performed and up to four tests can be congured. Each click on the Add Test button
adds one test. Each click on the Remove Test button removes one test.
Close OptionTests 1-4
Select the specic closing prole to be used for each test. Choose from the Closing
Prole 1 or Closing Prole 2 options.
Delay (seconds)Tests 2-4
Specify the delay in seconds between each test. (Minimum: 1.80 for Time 1, 10.00 for
Time 2, and 30.00 for Time 3; Maximum: 655.00 seconds; Default: the minimum value;
Increment: 0.01)
S&C Instruction Sheet 766-530 117
Loop Restoration

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C IntelliRupter PulseCloser and is the answer not in the manual?

S&C IntelliRupter PulseCloser Specifications

General IconGeneral
BrandS&C
ModelIntelliRupter PulseCloser
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals