Message Duration
When the Test by Message mode is selected, the Message Duration eld will set the
number of messages that will be sent. (Range: 100-1,000; Step: 100; Default: 100)
Repeat
This is the retest schedule interval: None, Daily, Weekly, or Monthly setting. (Default:
Daily)
Time Between Messages
This is the number of seconds between each message transmission. The rst test message
is sent to each node sequentially. Then the second test message is sent to each node
sequentially, etc. (Range: 1-120; Step: 1; Default: 5)
Next Start Time
This eld is blank until the rst start time is entered. After the next test, the eld updates
automatically to show the next time a test will start. The Next Start Time setting is
determined by the previous start time (entered manually or updated automatically from
the last test) and the congured Repeat interval setting. Users are not allowed to set a
date or time in the past.
Link Keep Alive Test Section
When a TCP or UDP connection remains idle it may shut down. A Link Keep Alive event
is not a test, but to keep all links active it periodically sends a single message to every
node. If more than one message is congured for the Scheduled Test, the Link Keep Alive
event only sends the rst congured message. It also records statistics for the message
transmissions.
Frequency
This sets how often a Link Keep Alive test is run. (Range: 1-60 minutes; Step: 1 minute;
Default: 4 minutes)
Ping and Serial Link Test Section
A ping test is a manually sent Ethernet ping to a specic IP address. A serial link test is
a manually sent ping over a serial port to a specic DNP address.
Ping Test Timeout
If a ping test return takes longer than this congured value, the ping test event will timeout
and stop waiting for a response. Set this value in milliseconds. (Range: 500-5,000; Step:
500; Default: 5,000)
Serial Link Test Timeout
If a serial link test return takes longer than this congured value, the serial link test
event will timeout and stop waiting for a response. Set this value in milliseconds.
(Range: 500-30,000; Step: 500; Default: 5,000)
158 S&C Instruction Sheet 766-530
Communication Setup

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C IntelliRupter PulseCloser and is the answer not in the manual?

S&C IntelliRupter PulseCloser Specifications

General IconGeneral
BrandS&C
ModelIntelliRupter PulseCloser
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals