On Next Power-up, Use Settings From:
Select from the drop-down list. Select the Control Once or Control Always options
when the IntelliRupter fault interrupter was previously congured and those control
settings will be used. When the protection-and-control module is a replacement, select
the Base Memory option. The replacement module will be congured with the settings
stored in the base memory module. Settings are stored for: Block Ground Trip, Use 2nd
Closing Prole, HLT Set by SCADA, HLT Set by Wi-Fi, HLT Set by IntelliLink,
Block Circuit Testing, Block Test on Backfeed, Block SEF Trip, Block Single
Phase Trip, Remote Operation, and the active General functions.
On Next Power-up, Use Command States From:
Select from the drop-down list. Select the Control Once or Control Always options
when the IntelliRupter fault interrupter was previously congured and those command
states will be used. When the protection-and-control module is a replacement, select
the Base Memory option. The replacement module will be congured by the command
states stored in the base memory module. States are stored for these functions:
• Ground/Neg-Seq Trip Enable/Block
• Loop Restoration Enable/Disable
• Circuit Testing Enable/Block
• Test on Backfeed Enable/Block
• Sensitive Earth Trip Enable/Block
• Single-Phase Trip Enable/Block
• Remote Operation Enable/Disable
• HLT Set by SCADA, HLT Set by IntelliLink.
• Latched Overcurrent Execute
When the GROUND TRIP manual lever is in the Blocked state, it takes precedence
over the saved user command state.
When the HOT LINE TAG manual lever is in the On state, it takes precedence over
the saved user command state.
On Next Power-up, Use Netlist From:
Select from the drop-down list. Select the Control Once or Control Always options
when the IntelliRupter fault interrupter was previously congured and that Netlist will
be used. When the protection-and-control module is a replacement, select the Base
Memory option. The replacement module will be congured with the Netlist stored in
the base memory module.
Timed Shut Down after Loss of AC Voltage
Select the Yes option to require timer expiration before shutdown. The No option is the
default.
Time to Disconnect Battery After Loss of Ac Voltage
This setting congures the timer. (Range: 1-240; Step: 1 minute; Default: 120)
S&C Instruction Sheet 766-530 17
General Setup