On Next Power-up, Use Settings From:
Select from the drop-down list. Select the Control Once or Control Always options
when the IntelliRupter fault interrupter was previously congured and those control
settings will be used. When the protection-and-control module is a replacement, select
the Base Memory option. The replacement module will be congured with the settings
stored in the base memory module. Settings are stored for: Block Ground Trip, Use 2nd
Closing Prole, HLT Set by SCADA, HLT Set by Wi-Fi, HLT Set by IntelliLink,
Block Circuit Testing, Block Test on Backfeed, Block SEF Trip, Block Single
Phase Trip, Remote Operation, and the active General functions.
On Next Power-up, Use Command States From:
Select from the drop-down list. Select the Control Once or Control Always options
when the IntelliRupter fault interrupter was previously congured and those command
states will be used. When the protection-and-control module is a replacement, select
the Base Memory option. The replacement module will be congured by the command
states stored in the base memory module. States are stored for these functions:
Ground/Neg-Seq Trip Enable/Block
Loop Restoration Enable/Disable
Circuit Testing Enable/Block
Test on Backfeed Enable/Block
Sensitive Earth Trip Enable/Block
Single-Phase Trip Enable/Block
Remote Operation Enable/Disable
HLT Set by SCADA, HLT Set by IntelliLink.
Latched Overcurrent Execute
When the GROUND TRIP manual lever is in the Blocked state, it takes precedence
over the saved user command state.
When the HOT LINE TAG manual lever is in the On state, it takes precedence over
the saved user command state.
On Next Power-up, Use Netlist From:
Select from the drop-down list. Select the Control Once or Control Always options
when the IntelliRupter fault interrupter was previously congured and that Netlist will
be used. When the protection-and-control module is a replacement, select the Base
Memory option. The replacement module will be congured with the Netlist stored in
the base memory module.
Timed Shut Down after Loss of AC Voltage
Select the Yes option to require timer expiration before shutdown. The No option is the
default.
Time to Disconnect Battery After Loss of Ac Voltage
This setting congures the timer. (Range: 1-240; Step: 1 minute; Default: 120)
S&C Instruction Sheet 766-530 17
General Setup

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C IntelliRupter PulseCloser and is the answer not in the manual?

S&C IntelliRupter PulseCloser Specifications

General IconGeneral
BrandS&C
ModelIntelliRupter PulseCloser
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals