EasyManua.ls Logo

S&C IntelliRupter PulseCloser - Page 19

S&C IntelliRupter PulseCloser
181 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 6. The Setup>General>Site-Related>System screen.
System Section
Pole 1 Phase Label (1 character)
This is the label for Pole 1. See Figure 6.
Pole 2 Phase Label (1 character)
This is the label for Pole 2.
Pole 3 Phase Label (1 character)
This is the label for Pole 3.
Information about Phase Rotation Settings
The IntelliRupter fault interrupter measures phase rotation (123, 132, or Undened)
using both terminal X & Y phase voltages. If viable voltage is present on both terminals,
only terminal X is used when determining phase rotation.
When the IntelliRupter fault interrupter control powers up it may take sev-
eral minutes before the measured phase rotation is displayed on the Metering
screen. Until then, the Metering screen displays the phase rotation setting on the
Setup>General>System>Phase Rotation screen.
Until terminal-X phase rotation is measured, the IntelliRupter fault interrupter
measures positive and negative sequence voltage based on the 123 or 132 setting in
Setup>General>System>Phase Rotation screen.
In the event the phase rotation setting on the Setup>General>System>Phase
Rotation screen results in the IntelliRupter fault interrupter detecting both terminals
X & Y have higher negative sequence voltages than positive sequence voltages, the
Metering screen will initially display negative sequence voltages for both terminals.
After about 1 minute these terminal X & Y negative sequence voltages will change to
positive sequence voltages.
S&C Instruction Sheet 766-530 19
General Setup

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Related product manuals