Hot Line Tag Prole—The Hot Line Tag mode can be set locally with the HOT LINE
TAG lever and with an IntelliLink or SCADA command. The Hot Line Tag prole allows
the user to select alternate overcurrent, voltage, and frequency protection with one trip-
to-lockout, and it blocks all closing commands. For more information, see the “Manual
Hot Line Tag” section in Instruction Sheet 766-510, “S&C IntelliRupter® PulseCloser®
Fault Interrupter: Installation.”
Closing Proles—A Closing Prole operation is used when the IntelliRupter fault
interrupter is closed from the Open and Locked Out position. The Synch Check mode
may be used before closing, or a PulseClosing Technology operation, to test for faults.
Overcurrent, voltage, and frequency protection may all be set for one trip to lockout.
Closing Prole operations are time-limited and will switch to the assigned general
prole when closing is successful. A second Closing Prole operation with different
parameters than the rst Closing Prole operation may be selected.
Single-Phase Trip—IntelliRupter fault interrupters can be congured to open only the
faulted phases for an overcurrent trip signal.
Cold Load Pickup—The Cold Load Pickup modier can be set to modify overcurrent
protection after an extended outage.
Ground Trip Block—The Ground Trip Block mode prevents an inadvertent trip
caused by the imbalance created by diverting current on one or two phases through
single-phase bypass switches.
DNP Point Mapping—DNP points for the IntelliRupter fault interrupter can be mapped
to different point numbers on a SCADA system. See S&C Instruction Sheet 766-560,
“IntelliRupter® PulseCloser® Fault Interrupter: DNP Points List and Implementation.”
8 S&C Instruction Sheet 766-530
Overview