EasyManua.ls Logo

S&C IntelliRupter PulseCloser - Frequency Trip

S&C IntelliRupter PulseCloser
181 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 56. The Setup>Protection>Hot Line Tag>Voltage and Frequency>Frequency Trip
screen.
Under Frequency Enabled
Specify the Yes or No (default) option.
Under Frequency Threshold
This is the frequency (in hertz) below which a Trip operation will occur. Enter between
47 and 60 Hz, but the setting will be valid only if it falls within the Range: System
Frequency – 3 to System Frequency. (Minimum: System Frequency - 3 Hz; Maximum:
System Frequency; Default: System Frequency - 0.5 Hz; Increment: 0.01)
Over Frequency Enabled
Specify the Yes or No (default) option.
Over Frequency Threshold
This is the frequency (in hertz) above which a Trip operation will occur. Enter between
50 and 62 Hz, but the setting will be valid only if it falls within the Range: System Frequency
to System Frequency + 2. (Minimum: System Frequency; Maximum: System Frequency
+ 2 Hz; Default: System Frequency + 0.50 Hz; Increment: 0.01)
Frequency Time to Trip
This is the time (in seconds) the Underfrequency or Overfrequency Threshold
setting must be exceeded for a Trip operation to occur. (Range: 0.06-600.00; Step: 0.02;
Default: 30.00)
Reset Time
This is the time (in seconds) good frequency must be present for the Frequency element
to reset. (Range: 0.06-600.00; Step: 0.02; Default: 1.00)
Frequency Trip Section
Each Hot Line Tag prole has settings for multiple Frequency Trip elements. See
Figure 56.
96 S&C Instruction Sheet 766-530
Protection Setup

Table of Contents

Other manuals for S&C IntelliRupter PulseCloser

Related product manuals