S&C Instruction Sheet 461-509 33
Name Description
Data
Type of
Value
Range of Value
enableSingleUnitOperation
This setting enables or disables the single-unit Drop Open feature in the gateway,
independent of the individual settings for the TripSaverII recloser. When set
to “true,” the singe-unit Local Drop Open feature is enabled and will operate
according to the settings defined on the Gang/Local tab for each TripSaverII
recloser. When set to “false,” the Single Unit Operation feature will not operate.
Binary True or False
remoteDropOpenEnabled
This setting enables or disables the Remote Drop Open feature in the gateway,
independent of the individual settings for the TripSaverII recloser. When set to
“true,” the Remote Drop Open feature is enabled and will operate according to
the settings defined on the Gang/Local tab for each TripSaverII recloser. When
set to “false,” the Remote Drop Open feature will not operate.
Binary True or False
IECtoggle
This setting determines the SCADA protocol the gateway will use. When set to
“false,” the gateway will use DNP3. When set to “true,” the gateway will use IEC
60870-5-104. For more details on IEC 60870-5-104, refer to S&C Instruction Sheet
461-519.
Boolean True or False
timeSyncSource
This setting specifies the source(s) the gateway will use for time synchronization.
When set to “gps,” the gateway will only rely on GPS for time synchronization.
When set to “SCADA,” the gateway will only synchronize with the DNP3 SCADA
master. When set to “gpsScada,” the gateway will rely on GPS as its highest
priority time synchronization source and use DNP3 as a backup method.
String
gps, scada,
gpsScada
Table 1. Import and Export ConfigDB Parameters —Continued
Conguring the Communications Gateway