S&C Instruction Sheet 461-509 53
recloser is configured to work in a gang. For this feature to work, the Receive Local
Drop Open setting must be enabled in both the gateway and the TripSaverII recloser by
toggling the appropriate buttons to the On position. Click on the Save button after
making the desired settings. See Figure 48.
Figure 48. Enabling the single-unit Local Drop Open operation.
The Gang Operation feature is enabled by toggling the Enable Gang Operation
button to the On position.
To be a member of a gang operation group, the TripSaverII must have the Receive
Local Drop Open feature enabled in both the communications gateway and the
TripSaverII recloser by toggling both the Enable in Gateway and Enable in TripSaverII
buttons to the On position as well as having the Include in Gang button toggled to the
On position. Click on the Save button after making the desired settings.
The Enable in Gateway toggle button must be set to allow the gateway to gang
operate the TripSaverII recloser, while Enable in TripSaverII toggle button enables the
same drop-open capability in the TripSaverII recloser itself. The Enable in TripSaverII
setting can also be modified via SCADA using a DNP3 command or with the TripSaverII
Service Center Configuration Software. Both the Enable in Gateway and Enable in
Tr ipSaverII toggle buttons must be toggled to the On position for a TripSaverII recloser
to drop open because of a gang operation or by using the green Drop Open button under
the “Perform Local Command” column.
Conguring the Communications Gateway