S&C Instruction Sheet 461-509 55
The Local Drop Open Retry Time (seconds) field configures the time between
drop-open commands given to the reclosers, either directly by clicking the Perform
Local Command button or when configured for gang operation. (Range: 0-3600 seconds;
Default: 10)
The Local Drop Open Max Retries field configures the maximum number of Gang/
Local operation commands to be given to the reclosers configured for Gang/Local
operation. (Range: 0-2,592,000)
After making the desired settings, click on the Save button to save the configuration.
The Perform Gang Trip button can be clicked to perform a local Gang Operation
function on user request. When this button is clicked, the user will be asked to provide
a walkaway time interval, in seconds. After this time interval, the gateway will perform
the Gang Trip operation.
WARNING
Enter a walkaway time long enough to give any personnel underneath the TripSaverII
reclosers enough time to walk away. Do not stand underneath the TripSaver II
reclosers during a gang operation. Failure to walk away could result in severe
personal injury.
The Cancel Drop Open Retries button will be enabled when a Gang Operation
procedure is active and performing periodic retries. When this button is clicked, the
communications gateway will immediately halt the retries and will abandon the Drop
Open operation. See Figure 51.
Figure 51. Performing a Gang Trip operation.
Conguring the Communications Gateway