62 S&C Instruction Sheet 461-509
Status Point: These point numbers represent what the SCADA system will see in response
to a static or event data request or an unsolicited event response.
Code Description: Point codes representing specic status points may be assigned to
individual SCADA point numbers. A full list of code-description denitions is found in
S&C Instruction Sheet 461-560, “TripSaver® II Communications Gateway: DNP Points
List and Implementation.” Code descriptions are defined by selecting the Code
Description eld in line with the respective Status Point eld. A drop-down dialog
box will appear with code denitions for all TripSaver II reclosers paired with the
communications gateway. See Figure 60. When a code denition has been chosen, select
the Check Mark icon to nalize it. Removal of a code selection can be performed by
selecting the blank row in the pull-down menu and clicking on the check mark. This will
result in the eld being displayed as empty. Finally, click on the Save button.
Figure 60. The Code Description drop-down menu.
Class: This is the DNP event class in which this point can be placed. Specify Class 1,
Class 2, or Class 3, or choose the No Event option if event data reporting is turned off
for that point.
Conguring the Communications Gateway