74 S&C Instruction Sheet 461-509
Conguring the Communications Gateway
STEP 3. On the DNP3 Outstation Settings screen, Command (Binary Output) eld,
a Binary Output status point must be congured with code description
“1: Communication Gateway remote web user interface switch.” See Figure 70.
Figure 70. Configuring the Remote Web UI DNP3 command (binary output).
STEP 4. See Figure 71. On the DNP3 Outstation Settings screen, Status (Binary
I nput) eld, two Binary Input status points must be congured with the
following code descriptions:
“8. Communication Gateway remote web user interface access enabled”
“9. Communication Gateway remote web user interface access enable via
DNP3”
Figure 71. Configuring the Remote Web UI DNP3 status points (binary inputs).