Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG

Congure
6-7
6
Universal input
Properties,typesandPG5Dev.Cong.Settings
Properties
Type
7
1)
Type
8
1)
PG5DeviceCongurator
Settings
2)
0…10 V Yes Yes 0…10 V
2.5kΩ No Yes 
10kΩ No Yes 
100kΩ(NTC20kΩ)and(NTC10kΩ Yes No 
PT/NI 1000 No Yes PT/NI 1000 L&S
Dry contact

 
Pull-up voltage: 10 V
Yes No Dry contact
Digital Input 24 VDC
Input delay: Min. 16 ms
Closed: Voltage < 1 V
Open: Voltage > 5 V
Yes Yes Digital
1)
See also bottom of table. .
PCD7.LRSx-P5 room controllers: Overview of connections and functions (by model)
or
PCD7.LRLx-P5 room controllers: Overview of connections and functions (by model)
2)
