Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG Communication
5
5-17
Modbus on PCD7.LRxx-P5 RS-485 interfaces
5.4.3 Media Mapping
PCD7.LRxx-P5
The following tables are a complete and detailed view, including Modbus address-
ing.
Modbus-Coils / PCD-Flags
PCD7.LRL2-P5 PCD7-LRL4-P5 PCD7.LRL5-P5 PCD7.LRS4-P5 PCD7.LRS5-P5
Descrip-
tion
Modbus
coil
address
address
Modbus
coil
address
address
Modbus
coil
address
address
Modbus
coil
address
address
Modbus
coil
address
address
PLC
variables
0 0 0 0 0 0 0 0 0 0
... ... ... ... ... ... ... ... ... ...
3999 3999 3999 3999 3999 3999 3999 3999 3999 3999
Universal
Input 0
4000 4000 4000 4000 4000 4000 4000 4000 4000 4000
Universal
Input 1
4001 4001 4001 4001 4001 4001 4001 4001 4001 4001
Universal
Input 2
4002 4002 4002 4002 4002 4002 4002 4002 4002 4002
Universal
Input 3
4003 4003 4003 4003 4003 4003 NA NA NA NA
Universal
Input 4
4004 4004 4004 4004 4004 4004 NA NA NA NA
Universal
Input 5
4005 4005 4005 4005 4005 4005 NA NA NA NA
Universal
Input 6
NA NA 4006 4006 4006 4006 NA NA NA NA
Universal
Input 7
NA NA 4007 4007 4007 4007 NA NA NA NA
Universal
Input 8
NA NA 4008 4008 4008 4008 NA NA NA NA
Universal
Input 9
NA NA 4009 4009 4009 4009 NA NA NA NA
… … … … … … … … … … …
Relay 0 4020 4020 4020 4020 4020 4020 4020 4020 4020 4020
Relay 1 4021 4021 4021 4021 4021 4021 4021 4021 4021 4021
Relay 2 4022 4022 4022 4022 4022 4022 4022 4022 4022 4022
Relay 3 4023 4023 4023 4023 4023 4023 4023 4023 4023 4023
… … … … … … … … … … …
Triac 0 4030 4030 4030 4030 4030 4030 4030 4030 4030 4030
Triac 1 4031 4031 4031 4031 4031 4031 4031 4031 4031 4031
Triac 2 4032 4032 4032 4032 4032 4032 NA NA NA NA
Triac 3 4033 4033 4033 4033 4033 4033 NA NA NA NA
… … … … … … … … … … …
LED
Output
4040 4040 NA NA NA NA NA NA NA NA
The status of universal inputs (addresses 4000 to 4009) are only available in digi-
tal mode (Digital in & Dry contact).