59
Configuration
Command Menu/MR-2300 Config/Features/
12.Common Supervisory Relay
[X] ENABLE ->Default
[ ] DISABLE
Supervisory relay
used as alarm
relay
If enabled, the Common
Supervisory Relay behaves
as a common alarm relay. If
disabled, it behaves as a
common supervisory relay
Command Menu/MR-2300 Config/Features/
13.Signal Isolators
[ ] ENABLE
[X] DISABLE ->Def
Isolators on
signal circuits
Enable this function only when
suite isolators are used
(Canada only)
Command Menu/MR-2300 Config/Features/
14.Strobe Type
[X] NORMAL ->Default
[ ] SECUTRON
[ ] FARADY
[ ] WHEELOCK
[ ] GENTEX
[ ] SYSTEM SENSOR
Strobe
Use this menu to select the
manufacturer of the strobes
used in the system. The
selection is system-wide and
applies to all indicating circuits
configured as strobes. For
NORMAL strobes there is no
synchronization, while other
strobes are synchronized and
use manufacturer’s protocol to
synchronize the strobes.
Command Menu/MR-2300 Config/Features/
15.Signal Rate (Evacuation Code)
[X] TEMPORAL->Def
[ ] CONTINOUS
[ ] MARCH TIME
[ ] CALIFORNIA
Signal rate
Use this menu to set the rate
at which the indicating circuits
will sound.
Command Menu/MR-2300 Config/Features/
16. Active EOL
[X] DISABLE->Default
[ ] ENABLE
Active end-of-line
Enable this function if using
an Active EOL. If MR-2300-A
is used, this function should
be enabled since the Class A
Converter has built in Active
EOL resistors.
Table 9 Feature Config Menu (Continued)
Feature Default
Name in the
Configuration Utility
Description
Common Supv. Relay
[X] ENABLE
Sig-Sil. Isolator
[X] DISABLE