75
Configuration
11.11.5Auto Test Time and Cellular Report Date
If the Cellular report date is set to 0, then the dialer alternates between Lines 1 and 2 when
performing the automatic test. If the Cellular report date is not set to 0, then the automatic test
is performed on Line 1 except on the Cellular report date, when it is performed on Line 2. See
examples in Table 11.
Command Menu-->Dialer-Config
11.11.6Dialer Enable/Disable
Command Menu/Dialer-Config/Time Parameter
3.Auto test time
00:30 ->Default
Use this function to set the time for
the automatic test. When this test is
performed, the test report is sent to
the monitoring station. This test
must be performed at least once a
day. The time is in 24 hour format,
which means 00:30 is 30 minutes
after midnight.
The Auto test time can be
configured to:
12:00 a.m. to 5:59 a.m.: test every
24 hours
6:00 a.m. to 11:59 a.m.: test every 6
hours
12:00 p.m. to 23:59 p.m.: test every
12 hours
If the Cellular report date is set to 0,
then the test alternates between
Line 1 and Line 2. See section
11.11.5 for more information.
Table 11 Auto Test Time and Cellular Report Date
Cellular Report Date Auto Test Time Line 1 Tested Line 2 Tested
0 00:30
12:30 a.m. every other day
(alternates with Line 2)
12:30 a.m. every other day
(alternates with Line 1)
0 6:00 6:00 a.m. and 6:00 p.m. 12:00 p.m. and 12:00 a.m.
0 12:00 12:00 p.m. 12:00 a.m.
15 00:30
12:30 a.m. every day
except on the 15th of the
month
12:30 a.m. on the 15th of
the month
15 6:00
6:00 a.m., 12:00 p.m., 6:00
p.m., and 12:00 a.m. every
day except on the 15th of
the month
6:00 a.m., 12:00 p.m., 6:00
p.m., and 12:00 a.m. on
the 15th of the month
15 12:00
12:00 p.m. and 12:00 a.m.
every day except on the
15th of the month
12:00 p.m. and 12:00 a.m.
on the 15th of the month
[X] ENABLE ->Default
[ ] DISABLE
The dialer is enabled by default.
When the dialer is enabled or
disabled, a warning message
appears.
Warning: The dialer cannot report
any event to the monitoring station
if it is disabled.
Auto-Test Time
00:30
Dialer Ena/Dis
[X] ENABLE
------Warning-------
Dialer Disabled!!!

Table of Contents

Other manuals for Secutron MR-2306-DDR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2306-DDR and is the answer not in the manual?

Secutron MR-2306-DDR Specifications

General IconGeneral
BrandSecutron
ModelMR-2306-DDR
CategoryControl Panel
LanguageEnglish

Related product manuals