Supported Protocols/Devices
10.3.6 Freeze trouble
If the device has detected a freeze condition, (e.g. the temperature is below 41F / 5 C) then
the panel will show a freeze trouble. Only model 2WT-B is capable of thermal detection; model
2W-B does not indicate any freeze trouble.
The LEDs on the i
3
smoke detectors provide a local visual indication of the detector status.
Table 8 i3 Detector Status
i
3
Detector Condition
Green LED Red LED
Power-up Blinks every 10 sec Blinks every 10 sec
Normal (Standby) Blinks every 5 sec OFF
Out of sensitivity (defective or dirty) OFF Blinks every 5 sec
Freeze trouble OFF Blinks every 10 sec
Alarm OFF Solid