EasyManuals Logo

Secutron MR-2306-DDR User Manual

Secutron MR-2306-DDR
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
48
Indicators, Controls and Operations
9.4.14 Non-Silenceable Strobes
Non-Silenceable Strobes will not be silenced when the “signal silence” key is pressed. For
synchronous strobes see section 10 on page 50. (Note: Strobes do not support any code
pattern.)
9.5 Evacuation codes
ContinuousOn 100% of the time
Temporal Code3 of 0.5 second on, 0.5 second off then, 1.5 second pause
March Code0.5 second on, 0.5 second off
California Code5 seconds on, 10 seconds off
Figure 29 Evacuation Codes
0.5s
5s
10s
0.5s
1.5s
Continuous
Temporal Code
March Code
California Code
Alert Code
0.5s
0.5s
0.5s
2.5s

Table of Contents

Other manuals for Secutron MR-2306-DDR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2306-DDR and is the answer not in the manual?

Secutron MR-2306-DDR Specifications

General IconGeneral
BrandSecutron
ModelMR-2306-DDR
CategoryControl Panel
LanguageEnglish

Related product manuals