49
Indicators, Controls and Operations
9.6 Fire Alarm Operation
In a basic system set up all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following: Non-Verified Alarm, Verified Alarm, Sprinkler Alarm, and Water flow
Alarm. If any of these alarm inputs occur when the panel is not already in alarm, the following
occurs:
The Buzzer sounds steadily
If Fire Drill is active, it is cancelled
The Common Alarm Indicator turns on
The Auxiliary Common Alarm Relay activates if Aux Disconnect is not active
The Auto Signal Silence Timer, if configured, starts
The Signal Silence Inhibit Timer, if configured, starts
All connected relays programmed to the input are activated (provided that Aux
Disconnect is not active)
Non-disconnected strobes associated with the input are activated
Non-disconnected signals associated with the input are activated at the evacuation rate
Subsequent alarms when the panel is already in alarm cause the following:
The alert buzzer sounds steadily
If Signals have been silenced as a result of the Signal Silence button or the Auto Signal
Silence Timer, Signals are resounded as they were before Signal Silence, the Signal
Silence Indicator is turned off, and the Auto Signal Silence Timer, if configured, is
restarted
Any additional non-disconnected strobes associated with the new input are activated
continuously
Any additional non-disconnected signals associated with the new input are activated at
the evacuation rate

Table of Contents

Other manuals for Secutron MR-2306-DDR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2306-DDR and is the answer not in the manual?

Secutron MR-2306-DDR Specifications

General IconGeneral
BrandSecutron
ModelMR-2306-DDR
CategoryControl Panel
LanguageEnglish

Related product manuals