Field wiring
7.3 Connecting to a 3G4010CF Interface Device
For information on Compatible Receivers see “Appendix A: Compatible Receivers” on
page 85.
A typical connection is shown in Figure 24. The 3G4010CF is powered separately from the
PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive
Communications Interface Board (sold separately) is also required.
Figure 24 Connecting an FACP to a 3G4010CF Interface Device
Note: The DSC interface device 3G4010CF is required if the installation requires UL864
9th edition certification.
Telephone
Line A
Connection
E
O
L
Line 2
C.O.
Line 1
C.O.
PCS-100
P
OW
E
R
2
4
V
G
N
D
P
G
M4
G
N
D
1
4
V
NC
C
O
M
N
O
T
B
L
R
E
L
AY
J
W
1
AUX SUPPLY
+
-
+
-
To GSM/GPRS
Internet
Computer
Printer
SUR-GARD
SYSTEM IV
Internal IP: X.X.X.X
External IP: X.X.X.X
SG-Systems
Console 2.1
Default Gateway: X.X.X.X
Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
Router
Conventional
input configured
as 3G4010CF
radio trouble
MR-2300
3G4010CF
TRBL
A
L
A
R
M
R
E
L
A
Y
S
P
V
R
E
L
A
Y
T
R
B
L
R
E
L
A
Y
N
O
C
N
O
C
N
O
C
+
-
MR-2300 - 3G4010CF Connection - Typical Diagram
Typical Installation outside Canada
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010CF: 20 feet max.
- Contact DSC to reprogram the zone inputs to match the
FACP as shown in this diagram
- Use 2 DSC RM-2 Relays (sold separately) to supervise
both AC failure trouble and low battery trouble
- Install the DSC RM-2 Relays inside the 3G4010CF
enclosure above the PS4086
3G4010CF
TRBL
PGM4
C
O
M
Z
3
Z
2
Z
1
T
1
R
1
N
C
C
O
M
N
O
DSC
RM-2
Relay
E
O
L
-
PS4086
Transformer
Battery
DC IN
+12V
COM
AC IN
+
ACT
LBT
N
C
C
O
M
N
O
DSC
RM-2
Relay
E
O
L
-
+
BAT+
BAT-
3G4010CF
3G4010CF
TRBL
+
-
+
-
Conventional
input configured
as AC failure
trouble
Conventional
input configured
as low battery
trouble
i

Table of Contents

Other manuals for Secutron MR-2306-DDR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2306-DDR and is the answer not in the manual?

Secutron MR-2306-DDR Specifications

General IconGeneral
BrandSecutron
ModelMR-2306-DDR
CategoryControl Panel
LanguageEnglish

Related product manuals