Appendix B: Reporting
13.2 Security Industries Association SIA-DCS
SIA protocol does not define indicating zone troubles, but lists it as Untyped Zone Trouble/
Restore.
13.2.1 MR-2300 Event Codes
Event Description Event Family Qualifier
SIA Event
Code
Parameter
Phone Line #1 trouble detected Trouble New event LT 001
Phone Line #2 trouble detected Trouble New event LT 002
Phone Line #1 trouble restored Trouble Restore LR 001
Phone Line #2 trouble restored Trouble Restore LR 002
Failure to report to an Account Trouble New event RT Acct #
Report to an Account successful Trouble Restore YK Acct #
RS485 Communication Trouble Trouble New event YS 485
Periodic (24 hr) Test Event (Normal) Test New event RP 000
Periodic (24 hr) Test Event (Off-normal) Test New event RY 000
Manually initiated dialer test Test New event RX 000
Zone Fire Alarm Alarm New event FA NNN
Zone Fire Alarm restored Alarm Restore FH NNN
Zone Trouble detected Trouble New event FT NNN
Zone Trouble restored Trouble Restore FJ NNN
Zone Supervisory condition Supervisory New event FS NNN
Zone Supervisory restored Supervisory Restore FR NNN
Waterflow alarm Alarm New event WA NNN
Waterflow alarm restored Alarm Restore WH NNN
General Alarm Alarm New event QA NNN
General Alarm restored Alarm Restore QH NNN
Indicating Zone Trouble (*) Trouble New event UT NNN
Indicating Zone Trouble restored (*) Trouble Restore UR NNN
AC power lost Trouble New event AT 000
AC power restored Trouble Restore AR 000
Battery Low Trouble New event YT 000
Battery Low restored Trouble Restore YR 000
Ground Fault Trouble New event YP 000
Ground Fault restored Trouble Restore YQ 000

Table of Contents

Other manuals for Secutron MR-2306-DDR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2306-DDR and is the answer not in the manual?

Secutron MR-2306-DDR Specifications

General IconGeneral
BrandSecutron
ModelMR-2306-DDR
CategoryControl Panel
LanguageEnglish

Related product manuals