EasyManua.ls Logo

Seg WI Series - Inverse-Time Characteristics (I>, I>>, I>>>)

Seg WI Series
337 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.2.1.2 Inverse-Time Characteristics (I>, I>>, I>>>)
Characteris‐
tic
»Char«
Trip Delay Reset Delay
(only for »Reset Mode« =
“inverse time”)
t =
k
I
I>
α
-1
+ c
tChar
t =
τ
1 -
I
I>
α
tChar
k
[s]
c
[s]
α τ
[s]
α
IEC NINV 0.14 0 0.02 0.14 2
IEC VINV 13.5 0 1 13.5 2
IEC EINV 80 0 2 80 2
IEC LINV 120 0 1 120 2
IEEE MINV 0.0515 0.1140 0.02 4.85 2
IEEE VINV 19.61 0.491 1 21.6 2
IEEE EINV 28.2 0.1217 2 29.1 2
Characteris‐
tic
»Char«
Trip Delay Reset Delay
(only for »Reset Mode« =
“inverse time”)
t =
k
b -
c
I
I>
tChar
t =
τ
1 -
I
I>
α
tChar
k
[s]
b c τ
[s]
α
RINV 1.0 0.339 0.236 1.0 2
274 WIC1 WIC1-1.0-EN-MAN
11 Appendix
11.2.1.2 Inverse-Time Characteristics (I>, I>>, I>>>)

Table of Contents