EasyManua.ls Logo

Seg WI Series - Page 280

Seg WI Series
337 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.2.1.2.2 R Inverse [RINV] - Characteristic
»Char« = RINV
0.01 0.1 1 10 100
0.1
1
10
100
0.05
0.1
0.2
0.5
1
1.5
t / s
I / I> (multiples of pickup)
tChar=
wiPDOC_Z12
Fig. 82: RINV: reset delay (left half, I < I
>
) and trip delay (right half, I > I
>
), example for
I
Dyn.Lim.
= 20⋅I
>
.
See ╚═▷ “Explanation for All Characteristics (I>, I>>, I>>>)” and ╚═▷ “11.2.1.2 Inverse-
Time Characteristics (I>, I>>, I>>>)” for details.
Reset Delay
Various reset modes are available: Resetting via characteristic, delayed and instantaneous.
Trip Delay
If I
>
< I < I
Dyn.Lim.
, the trip delay is de󰊟ned by the characteristic.
For I > I
Dyn.Lim.
, the trip delay t is kept constant at t = t
Dyn.Lim.
.
280 WIC1 WIC1-1.0-EN-MAN
11 Appendix
11.2.1.2.2 R Inverse [RINV] - Characteristic

Table of Contents

Other manuals for Seg WI Series