Doc# E145701 2 - 10
2: Meter Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Max Input Wire Gauge: AWG#12 / 2.5mm
2
Fault Withstand: Meets IEEE C37.90.1
Reading: Programmable Full Scale to any PT
Ratio
Current Inputs
Class 10: 5A Nominal, 10A Maximum
Class 2: 1A Nominal, 2A Maximum (Shark®
50 is Class 10 only)
Burden: 0.005VA Per Phase Max at 11 Amps
Pickup Current: 0.1% of Nominal
Connections: O or U Lug Electrical Connection
(Figure 4.1)
Pass through Wire, 0.177" / 4.5mm
Maximum Diameter (Figure 4.2)
Quick Connect, 0.25" Male Tab
(Figure 4.3)
Fault Withstand (at 23
o
C): 100A/10sec., 300A/3sec.,
500A/1sec.
Reading: Programmable Full Scale to any CT
Ratio
Isolation
All Inputs and Outputs are galvanically isolated to 2500 VAC
Environmental Rating
Storage: (-20 to +70)
o
C
Operating: (-20 to +70)
o
C