Doc# E145701 2 - 11
2: Meter Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Humidity: to 95% RH Non-condensing
Faceplate Rating: NEMA12 (Water Resistant),
Mounting Gasket Included
Measurement Methods
Voltage, Current: True RMS
Power: Sampling at 400+ Samples per
Cycle on All Channels Measured
Readings Simultaneously
A/D Conversion: 6 Simultaneous 24 bit Analog to
Digital Converters
Update Rate
Watts, VAR and VA: Every 6 cycles
All other parameters: Every 60 cycles (The Shark® 50
meter’s update rate is every 60
cycles for all parameters)
Communication Format
1. Shark® 100 meter: RS485 (485P) or RJ45 (INP10) port through backplate
Shark® 100B meter: RJ45 (INP10) port through backplate is standard
Shark® 50 meter: RS485 (485P) port through backplate is optional
NOTE: KYZ pulse comes with both the RS485P and INP10 communication ports.
2. IrDA Port through faceplate (Shark® 50 meter does not have the IrDA port)
Protocols: Modbus RTU, Modbus ASCII, DNP
3.0 (V-3 and V-4 for Shark® 100)
Com Port Baud Rate: 9,600 to 57,600 b/s
Com Port Address: 001-247
Data Format: 8 Bit, No Parity